Pelican Wireless · Thermostat

Pelican Wireless TC2 Commercial Thermostat with Humidity

Connected commercial thermostat with temperature and humidity sensing plus dedicated humidity-control outputs.

Pelican Wireless TC2

Pelican Wireless TC2

Will this work with my system?

Match your equipment to these requirements before ordering.

Works with

  • 24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
  • Staging: Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.

System requirements

  • Supply voltage: 24 V AC nominal, 60 Hz; operating range 23–30 V AC
  • Power: Hardwired AC
  • Wiring: Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
  • Electrical load limits: 2.0 A running on Y, Y2, W, W2 and G; TC2 Hu/Dh: 1.0 A running
  • Connection: Pelican mesh network; not Wi-Fi

Limitations & exclusions

  • Not a battery-powered or wire-free thermostat; hardwired power is required.

Check before you buy

  1. Match the equipment type, stages and fan speeds to the exact TC-model wiring diagram; two-speed fan configurations reduce available stage outputs.
  2. Confirm a Pelican gateway and mesh connection for configuration and remote management.
  3. Check the R/C wiring or the included module’s minimum three-wire R/C/D connection against the installation guide.
Installation & configuration details
  • PEARL and TA1 are optional accessories with application-specific wiring and configuration. A TC thermostat supports one PEARL and one TA1.
  • PEARL demand-based ventilation requires a CO2-sensing TC3 or TC4 and appropriate connected equipment.
Manufacturer documentation (2)

Use these documents to compare your exact model and configuration.

Overview

Part of the Pelican Wireless system. See the system overview for component roles and selection requirements.

TC2 is a Pelican touchscreen thermostat with built-in temperature and relative-humidity sensing. Dedicated humidification and dehumidification outputs operate appropriate external equipment; the TC2 does not include the CO₂ sensor found in TC3 and TC4.

Equipment and system requirements

A Pelican Gateway and mesh connection are required for configuration and remote management. The installation guide covers conventional equipment, heat pumps and two- or four-pipe fan coils. Output assignments depend on the equipment and fan-speed configuration. Zoning applications require their separate system design.

Occupant controls and scheduling

The touch interface provides local adjustment subject to administrator controls. Pelican scheduling supports daily, weekday/weekend and seven-day arrangements, temporary overrides, keypad restrictions and heating/cooling setpoint limits.

Installation considerations

TC2 requires hardwired 24 V AC power. The included limited-wiring module supports an R/C/D connection where at least three suitable conductors are available; it is not a battery-powered or wire-free installation.

Technical document notes

The manufacturer's product page and series datasheet disagree on enclosure dimensions and the lower ambient operating limit. Those optional figures are withheld pending hardware-revision confirmation.

Product details

Manufacturer
Pelican Wireless
SKU
190133
Model / MPN
TC2
Condition
New
Lifecycle
Current

Specifications

Power sources
Hardwired AC
Supply voltage
24 V AC nominal, 60 Hz; operating range 23–30 V AC
Communication protocols
Pelican mesh network; not Wi-Fi
Wireless standards
IEEE 802.15.4
Radio bands
2.4 GHz
Operating humidity
5–90% RH, non-condensing
Storage temperature
−20°F to 160°F
Remote management
Pelican web application through a Pelican Gateway
Supply current
105 mA at 24 V AC, 60 Hz
Control functions
Temperature; humidity
Equipment types
24 V AC conventional and heat-pump systems; two-/four-pipe fan coils per wiring guide; zoning requires the separate Pelican zoning design
Stage modes
Conventional: up to 2 heating / 2 cooling stages; heat pump: up to 2 compressor stages plus auxiliary/emergency heat. Two-speed fan configurations reduce available stage outputs.
Control signal types
Switched 24 V AC HVAC outputs; follow model-specific terminal diagrams
Scheduling modes
Daily, 5-2 and 7-day scheduling through the Pelican web application
Schedule periods per day
Up to 12 scheduled set times per day; maximum only, not a verified list of selectable counts
Keypad lockout
Administrator-managed and schedulable lockout; exact selectable levels not established
Setpoint limits
Administrator can limit heating and cooling setpoint adjustment; exact configurable bounds not established
System modes
Auto, Heat, Cool and Off; selectable modes depend on configuration
Local controls
Touchscreen
Hold options
Temporary schedule override and vacation mode; durations depend on configuration
Mounting methods
Interior wall or vertical single-gang electrical box; avoid metal surfaces/enclosures
C wire requirement
Configuration-dependent: direct wiring uses R/C; included wiring module supports a minimum three-wire R/C/D link. Not a wire-free or battery-powered installation.
Measured variables
Temperature and relative humidity
Contact ratings
2.0 A running on Y, Y2, W, W2 and G; TC2 Hu/Dh: 1.0 A running
Fan modes
Auto and On; High/Low selections depend on equipment configuration
Humidity control modes
Humidification and dehumidification via dedicated Hu/Dh outputs with appropriate external equipment; not merely humidity display

Documents & downloads

Optional components

Pelican Wireless PEARL

Pelican Wireless

Pelican Wireless PEARL Advanced Equipment Controller

Model PEARL SKU 190108

Pelican thermostat accessory for economizer, ventilation, variable-speed fan and modulating equipment control.

Supply voltage
24 V AC, 60 Hz
Communication protocols
Three-wire connection to a Pelican thermostat
Power sources
Hardwired AC

Price: $203.07

View details
Pelican Wireless TA1

Pelican Wireless

Pelican Wireless TA1 Temperature and Alarm Sensor

Model TA1 SKU 190104

Wired sensor accessory for temperature monitoring, averaging, or a dry-contact input on a compatible Pelican device.

Communication protocols
Pelican three-wire R/C/D connection
Mounting
Flat surface in a moisture-free location; device is not waterproof
Power sources
Hardwired AC

Loading price…

View details