Pelican Wireless · Zone controller
Pelican Wireless Z8 Zone Coordinator
Central HVAC zone coordinator for up to eight Pelican zone-thermostat demands, with equipment outputs and duct static-pressure control.
Will this work with my system?
Match your equipment to these requirements before ordering.
Works with
- Central HVAC zoning applications; exact retrofit and equipment sequence require engineering verification
- Staging: Up to three heating and three cooling stages; sequence and equipment configuration must be verified
System requirements
- Supply voltage: 24 V AC nominal, 60 Hz; operating range 23–30 V AC
- Power: Hardwired AC
- Connection: Pelican mesh network; not Wi-Fi
Check before you buy
- Match the full Z8 model number and hardware revision to the manufacturer's equipment manual and accessory list.
- Compare the equipment terminals, control voltage and required operating sequence with the model-specific installation diagrams.
Manufacturer documentation (2)
Use these documents to compare your exact model and configuration.
Overview
Part of the Pelican Wireless system. See the system overview for component roles and selection requirements.
The Z8 coordinates a central HVAC unit serving multiple zones. Pelican zone thermostats send demand information over the wireless mesh network, and the Z8 adjusts the central equipment. It supports up to eight zone-thermostat demands; a bypass damper does not count as a zone.
Control and sensing
The controller provides binary and modulating outputs, temperature inputs and differential-pressure sensing. Pelican documents sequences for coordinating heating, cooling, ventilation and supply-duct static pressure. The applicable sequence depends on the air-handling equipment, dampers, fan control and installed sensors.
System requirements
A Pelican Gateway and Internet connection are needed for configuration and remote management. The installation manual states that configured devices retain local operation if Internet access is lost. Individual zones need the appropriate Pelican thermostats and damper/reheat interfaces; the Z8 is not a replacement for a network gateway.
Installation considerations
The Z8 uses a 24 V AC supply. Its central-equipment outputs, temperature inputs and pressure connections must be matched to the installation using the zone coordinator and damper-control manuals. Use the zoning sequence guide when assessing the complete system; a generic thermostat compatibility label is insufficient.
Technical document notes
Pelican’s linked documents disagree on supply current, relay current and enclosure depth. These ratings are omitted from the specification table pending confirmation of the applicable Z8 hardware revision. Review the installation guide and manufacturer confirmation before sizing the supply, selecting switched loads or planning enclosure clearances.
Product details
- Manufacturer
- Pelican Wireless
- SKU
- 190115
- Model / MPN
- Z8
- Condition
- New
- Lifecycle
- Current
Specifications
- Power sources
- Hardwired AC
- Supply voltage
- 24 V AC nominal, 60 Hz; operating range 23–30 V AC
- Communication protocols
- Pelican mesh network; not Wi-Fi
- Wireless standards
- IEEE 802.15.4
- Radio bands
- 2.4 GHz
- Operating humidity
- 5–90% RH, non-condensing
- Storage temperature
- −20°F to 160°F
- Remote management
- Pelican web application through a Pelican Gateway
- Control functions
- Central equipment, zoning and supply-duct static-pressure control
- Device capacity
- Up to eight zone-thermostat demands; bypass damper not counted as a zone
- Io channels
- Four analog outputs and two analog inputs (0/2–10 V DC, configured by function); three 10K Type II thermistor inputs; differential-pressure ports
- Relay count
- Eight binary outputs; contact ratings require revision confirmation
- Sensor input count
- Three thermistor inputs, plus separate analog and differential-pressure inputs
- Measurement channels
- Differential pressure: 0–8 in. water column; temperature detection: −20 to 180°F
- Stage modes
- Up to three heating and three cooling stages; sequence and equipment configuration must be verified
- Internet requirement
- Internet required for initial configuration and remote features; configured equipment control continues locally during loss of Internet
- Operating temperature
- −4°F to 160°F
- Equipment types
- Central HVAC zoning applications; exact retrofit and equipment sequence require engineering verification
Documents & downloads
- Installation guide (PDF)
Z8 Installation Guide (PDF)
- Specification sheet (PDF)
Z8 Datasheet — see technical document notes (PDF)
- Pelican Zoning SOO — system reference (PDF) (PDF)
- Installation guide (PDF)
Zone Damper Installation Guide — system reference (PDF)
- Wireless Network and Installation Planning Guide — system reference (PDF) (PDF)
- Section 23 09 22: Climate Management Controls for HVAC — system reference (PDF) (PDF)
- Network Security — system reference (PDF) (PDF)
- Wireless Communication Frequency — system reference (PDF) (PDF)
- Warranty (PDF)
Warranty — system reference (PDF)